How to calculate the overall heat transfer coefficient of a tubular heat exchanger?

Dec 12, 2025Leave a message

As a supplier of tubular heat exchangers, understanding how to calculate the overall heat transfer coefficient is crucial. This coefficient is a key parameter in the design, analysis, and performance evaluation of tubular heat exchangers. In this blog, I will delve into the details of calculating the overall heat transfer coefficient, providing you with a comprehensive guide that combines theoretical knowledge with practical considerations.

1. Understanding the Basics of Heat Transfer in Tubular Heat Exchangers

Before we start calculating the overall heat transfer coefficient, it's essential to understand the basic principles of heat transfer in tubular heat exchangers. A tubular heat exchanger consists of a bundle of tubes enclosed in a shell. One fluid flows through the tubes (tube - side fluid), while the other flows outside the tubes in the shell (shell - side fluid). Heat is transferred from the hot fluid to the cold fluid through the tube walls.

The heat transfer process involves three main resistances: the resistance on the tube - side fluid, the resistance of the tube wall, and the resistance on the shell - side fluid. The overall heat transfer coefficient (U) is related to these resistances and is defined by the following equation based on Fourier's law of heat conduction and Newton's law of cooling:

$$Q = U A \Delta T_{lm}$$

Titanium Tubular Heat ExchangerHorizontal Shell And Tube Heat Exchanger

where $Q$ is the rate of heat transfer, $A$ is the heat transfer area, and $\Delta T_{lm}$ is the log - mean temperature difference.

2. Calculating the Individual Heat Transfer Coefficients

Tube - side Heat Transfer Coefficient ($h_i$)

The tube - side heat transfer coefficient can be calculated using empirical correlations. One of the most commonly used correlations is the Dittus - Boelter equation for turbulent flow ($Re>10000$) in a smooth tube:

$$Nu = 0.023 Re^{0.8} Pr^n$$

where $Nu=\frac{h_i D_i}{k}$, $Re=\frac{\rho v D_i}{\mu}$, $Pr=\frac{C_p \mu}{k}$, $D_i$ is the inner diameter of the tube, $\rho$ is the density of the fluid, $v$ is the average velocity of the fluid, $\mu$ is the dynamic viscosity of the fluid, $C_p$ is the specific heat capacity at constant pressure, and $k$ is the thermal conductivity of the fluid. The exponent $n$ is 0.4 for heating and 0.3 for cooling.

For laminar flow ($Re < 2300$), the Sieder - Tate equation can be used:

$$Nu = 1.86\left(\frac{Re Pr D_i}{L}\right)^{\frac{1}{3}}\left(\frac{\mu}{\mu_w}\right)^{0.14}$$

where $L$ is the length of the tube and $\mu_w$ is the viscosity of the fluid at the wall temperature.

Shell - side Heat Transfer Coefficient ($h_o$)

Calculating the shell - side heat transfer coefficient is more complex due to the complex flow pattern of the shell - side fluid. One approach is to use the Kern method. The Kern method provides an estimate of the shell - side heat transfer coefficient based on the equivalent diameter ($D_e$) of the shell - side flow passage:

$$Nu = 0.36 Re^{0.55} Pr^{\frac{1}{3}}\left(\frac{\mu}{\mu_w}\right)^{0.14}$$

where $Re=\frac{\rho v_s D_e}{\mu}$, and $v_s$ is the shell - side fluid velocity. The equivalent diameter $D_e$ depends on the tube arrangement (e.g., triangular or square pitch).

3. Considering the Resistance of the Tube Wall

The resistance of the tube wall to heat transfer is given by:

$$R_{wall}=\frac{\ln\left(\frac{D_o}{D_i}\right)}{2\pi k_{wall}L}$$

where $D_o$ is the outer diameter of the tube, $D_i$ is the inner diameter of the tube, $k_{wall}$ is the thermal conductivity of the tube material, and $L$ is the length of the tube.

4. Calculating the Overall Heat Transfer Coefficient

The overall heat transfer coefficient based on the outer surface area of the tubes ($U_o$) can be calculated using the following equation, which takes into account the individual resistances:

$$\frac{1}{U_o}=\frac{D_o}{h_i D_i}+\frac{D_o \ln\left(\frac{D_o}{D_i}\right)}{2k_{wall}}+\frac{1}{h_o}+R_{f,i}\frac{D_o}{D_i}+R_{f,o}$$

where $R_{f,i}$ and $R_{f,o}$ are the fouling resistances on the tube - side and shell - side, respectively. Fouling is the deposition of unwanted materials on the heat transfer surfaces, which increases the resistance to heat transfer.

5. Practical Considerations and Examples

In practical applications, the calculation of the overall heat transfer coefficient requires accurate data on fluid properties, flow rates, tube dimensions, and fouling factors. Let's consider an example:

Suppose we have a Horizontal Shell and Tube Heat Exchanger with the following parameters:

  • Tube inner diameter $D_i = 0.02$ m
  • Tube outer diameter $D_o = 0.025$ m
  • Tube length $L = 3$ m
  • Tube material: Stainless steel with $k_{wall}=16$ W/(m·K)
  • Tube - side fluid: Water with $h_i = 2000$ W/(m²·K)
  • Shell - side fluid: Oil with $h_o = 500$ W/(m²·K)
  • Fouling resistance on the tube - side $R_{f,i}=0.0002$ m²·K/W
  • Fouling resistance on the shell - side $R_{f,o}=0.0005$ m²·K/W

We can calculate the overall heat transfer coefficient based on the outer surface area:

$$\frac{1}{U_o}=\frac{0.025}{2000\times0.02}+\frac{0.025\ln\left(\frac{0.025}{0.02}\right)}{2\times16}+\frac{1}{500}+0.0002\times\frac{0.025}{0.02}+0.0005$$

$$\frac{1}{U_o}=0.000625 + 0.000044+0.002 + 0.00025+0.0005$$

$$\frac{1}{U_o}=0.003419$$

$$U_o\approx292.5\ W/(m²·K)$$

6. Importance of the Overall Heat Transfer Coefficient

The overall heat transfer coefficient is a critical parameter in the design and operation of tubular heat exchangers. A higher overall heat transfer coefficient means more efficient heat transfer, which can lead to smaller heat exchangers, lower energy consumption, and reduced operating costs.

For different types of tubular heat exchangers, such as Single Pass Shell and Tube Heat Exchanger and Titanium Tubular Heat Exchanger, the calculation of the overall heat transfer coefficient is equally important. The material properties, flow configurations, and operating conditions of these heat exchangers will affect the individual heat transfer coefficients and, ultimately, the overall heat transfer coefficient.

7. Contact for Further Discussion and Procurement

If you are interested in tubular heat exchangers or need more information on calculating the overall heat transfer coefficient for your specific application, we are here to help. Our team of experts has extensive experience in the design and manufacturing of tubular heat exchangers. We can provide you with customized solutions based on your requirements.

Whether you need a standard tubular heat exchanger or a specialized one like a titanium tubular heat exchanger, we can offer high - quality products with excellent performance. Contact us to start a discussion about your heat transfer needs and explore the possibilities of procurement.

References

  • Incropera, F. P., DeWitt, D. P., Bergman, T. L., & Lavine, A. S. (2007). Fundamentals of Heat and Mass Transfer. John Wiley & Sons.
  • Kern, D. Q. (1950). Process Heat Transfer. McGraw - Hill.